| |
|
|
|
62.1-2013
COMPLY-DOAS
"Quick and Easy" Calculation Programs and
"Optimization" Procedures for compliance with ASHRAE
Standard 62.1-2013 DOAS, "Ventilation Rate Procedure".
Dedicated Outdoor Air System (DOAS) is used to supply outdoor air
directly to the building zones to satisfy occupant ventilation
requirements. Psychrometric calculations are included, based
on project location weather data (USA and International weather data
included), and provide recommended supply air conditions to offset
internal latent loads.
"Optimization"
routines identify worst-case zone(s) latent load and increase air
quantity to the critical zone(s), which can significantly reduce
required DOAS coil load.
Contents
62.1-2013 Comply-DOAS Package includes over (8) Programs, Tables, and
Forms that make Compliance with the ASHRAE 62.1-2013 "Ventilation Rate Procedure" very straightforward and
fast ("Quick and Easy"). Click the adjacent image for a full size
view of the Contents Page of the 62.1-2013 Comply-DOAS Software
Package. (Click Image to enlarge)
Note: Portions of the programs, tables, and design information
include excerpts from
ANSI/ASHRAE 62.1-2013: "©
2013 American Society of Heating, Refrigerating and
Air-Conditioning Engineers, Inc. (www.ashrae.org) Used by
permission."
|
|
Project Information
The "Basic Project Information" form should be the
first Form to be completed for every project.
Project information that is inserted in this Form is automatically
transferred to other Programs for use in calculations and for
documenting project data. (Click Image to enlarge)
|
|
Calculations Take-off Form
Blank Take-off Form sheets can be printed and used to
assemble all of the required input data for each air handling
system. Typical systems require only six input values
per zone. Input sheets can also be filled in on the computer
and the values copied to the input locations in the programs. (Click
Image to enlarge)
|
|
Outdoor Air Requirement Calculations
The purpose of ANSI/ASHRAE Standard 62.1-2013 is
to specify the minimum ventilation rates and indoor air quality that
will be acceptable to human occupants, and which is intended to
minimize the potential for adverse health effects. These Software Programs calculate the required
Outdoor Air Quantity for each Air Handling System, based on Space
Type/Application, Occupancy Level, and Floor Areas. (Click Image to
enlarge)
|
|
DOAS Supply Air
Temperature Calculations
Below the “Required Outdoor Air Intake Flow”
results and on the “DOAS-Loads” sheet are a series of
psychrometric-based calculations, to help determine the recommended
Supply Air Discharge Temperature.
The calculations are based on the Occupant (and
Miscellaneous) Latent load for the air handling system.
The resulting SA temperature is determined by psychrometric
calculations of: the Design Outdoor Air conditions (DB and WB) at
the project location; the anticipated occupant latent load, based on
the occupancy classification (expected activity level) and the total
number of occupants; humidity ratio difference required to offset
occupant latent load; psychrometric evaluation of the resulting
saturated wet bulb (WB) temperature, using elevation-corrected
factors for the project location; and the Total Heat requirement of
the cooling coil based on the Enthalpy difference between the Design
Outdoor conditions (minus Energy Recovery Wheel enthalpy reduction,
if applicable) and the calculated Supply Air Discharge Temperature
(Saturated Air Condition).
"Optimization"
routines perform multiple iterations to improve supply air
conditions to latent-load critical zones. Outdoor air quantity
is increased to the worst-case zone, based on internal latent loads,
which may then make another zone the new worst-case zone. OA
is then increased to the new critical zone, etc.. This
Optimization can significantly reduce the Total Load on the DOAS
unit, since the required supply air enthalpy difference is reduced
as the "drier" OA quantity is increased to the critical
zone(s). The final supply air condition is established to
maintain the designed space relative humidity.
|
|
|
|
Compliance Documentation
Compliance Documents can be printed after completing the
calculations and can be submitted as a Compliance Record to the
appropriate Building Department or Code Authority. It is recommended
that the following Output Pages, Assumptions, and Diagrams be
printed out, to assist with Building Department review:
- Printout of Air Handling Unit calculation results for each air
handling system (Note: number of printout pages for each air
handling system will depend on the number of zones) (Click Image
to enlarge)
- Copy of "Calculation and Design Assumptions"
- Table 6-1, Minimum Ventilation Rates In Breathing Zone
- Table 6-2, Zone Air Distribution Effectiveness
- Ventilation System Schematic Diagram
Portions of these documents are "© 2013 American Society of
Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org)
Used by permission."
(Click Image to enlarge)
|
|
Tables, Diagrams, and Forms
Before beginning input and calculations, the following Input
Forms, Tables, and Diagrams can be printed out, to assist with data
assembly:
- Calculations Take-off Forms (Multiple copies for air handling
systems with more than 12 zones)
- Table 6-1, Minimum Ventilation Rates In Breathing Zone
- Typical Zone Occupancy Take-off table and diagram
- Table 6-2, Zone Air Distribution Effectiveness
- Zone Air Distribution Effectiveness diagrams
- Ventilation System Schematic
- Copy of "Calculation and Design Assumptions"
Portions of these documents are "©
2013 American Society of
Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org)
Used by permission."
(Click any image to enlarge)
|
|
|
|
Disclaimer of Liability for ASHRAE, Inc.
In no event will ASHRAE (or American
Society of Heating, Refrigerating and Air-Conditioning Engineers,
Inc.) be liable for any damages arising out of the use or inability
to use the 62.1-2013 Comply programs or accompanying documentation,
however caused and on any theory of liability.
|
|
Prices/Orders
All of the above Programs, Forms, and Extras are included in the 62.1-2013
Comply-DOAS Package. Order now to assure that you will
receive the low "Limited Time Special Prices".
Available in I-P (Inch-Pound) units. Go to the Prices/Orders page for details.
|
Home | Software
| Prices/Orders | FAQ
| About Us | Contact
Us | Search
Copyright © 2014 - HVAC Design Solutions
|
|